ACT20X-HDI-SDO-RNO-S
Description:
Ex isolating switch amplifiers for Namur sensors:
- 1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,
to transmit and isolate Namur sensor signals from Ex zones 0,1,2 into the safe zone. - On the output side there is a potential-free relay contact with closing function and an alarm contact for status/error messages.
- The component can be configured using standard FDT/DTM software.
- Add-on housing for TS35 DIN rail installation.
- Dimensions: L/W/H 119.2/ 22.5/ 113.6
- Screw connection/ nominal cross-section 2.5 mm2
- Protection degree: IP20
- Input NAMUR sensor according to EN 60947 8 VDC / 8 mA sensor power supply 0 to 5 kHz input frequency wire-break detection.
- Output Relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2
- Alarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2.
- Auxiliary power 19 to 31.2 VDC.
- Power loss approx. 1.8 W
- Ambient
- Temperature range -20 °C to +60 °C
- Secure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each other
- Working voltage 300 V AC/DC at overvoltage category II and pollution degree 2
- Approvals cULus, ATEX IECEX, FM
- ATEX marking II 3 G ExnA NC IIC T4
- ATEX characteristic data U0 = 10, 6 V DC I0 = 12 mA DC P0 = 32 W