Back to Top
ACT20X-2SAI-2HAO-S
Description:
- Ex-output isolation amplifier with external power supply for a 2-channel HART transparent 2-channel output isolation amplifier for standard DC current signals. It can be used to transmit and isolate standard signals with a current of 4 to 20 mA from the safe zone to Ex zones 0, 1, and 2.
- Using a relay contact (NO), you can access status and error messages.
- The component can be set up with the help of common FDT and DTM software.
- Housing add-on for TS35 rail installation, Dimensions: L/W/H 119.2/ 22.5/ 113.6, nominal cross-section 2.5 mm2, screw connection; IP 20 protection level
- Input 2 x 4...20 mA
- Output 2 x 4...20 mA
- Load < 600 Ohm Kanal
- Accuracy < 0,1 % v.E
- Temperature coefficient < 0,01% v.E./°C (Tu)
- Alarm output relay 1 NO contact 250 V AC / 30 V DC @ 2A safe zone, 32 V AC @ 0.5 A/ 32 VDC @ 1 A Zone 2
- Auxiliary power 19...31.2 V DC
- Power loss approx. 3 W
- Ambient
- temperature range -20 °C... +60 °C
- Secure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each other
- Working voltage 300 V AC/DC at overvoltage category II and pollution degree 2
- Approvals cULus, ATEX IECEX, FM
- ATEX marking II 3 G ExnA nC IIC T4
- ATEX characteristic data U0 = 28 V DC, I0 = 93 mA DC, P0 = 650 mW