ACT20M-CI-CO-ILP-S

ZAR 0.00 ZAR 0.00
Out of stock
SKU
1176070000

Pricing available on request

ACT20M-CI-CO-ILP-S:

  • ACT20M: the slim solution.
  • Safe and space-saving (6 mm) isolation and conversion.
  • The power supply unit can be quickly installed by using the CH20M mounting rail bus.
  • Convenient configuration by DIP switch or FDT/DTM software.
  • extensive certifications from GL, DNV, ATEX, and IECEX.
  • high resistance to interference.

Dimensions and weights:

  • Depth: 114.3 mm.
  • Depth (inches): 4.5 inch.
  • Height: 112.5 mm.
  • Height (inches): 4.429 inch.
  • Width: 6.1 mm.
  • Width (inches): 0.24 inch.
  • Net weight: 80 g.

Temperatures:

  • Storage temperature: -40 °C - 85 °C.
  • Operating temperature: -25 °C - 70 °C.
  • Humidity at operating temperature: 0 - 95 % (no condensation).
  • Humidity: 40 °C / 93 % rel. humidity, no condensation.

Probability of failure:

  • SIL in compliance with IEC 61508: None.
  • MTBF: 699 a.

Environmental Product Compliance:

  • REACH SVHC: Lead 7439-92-1.
  • SCIP: 2f6dd957-421a-46db-a0c2-cf1609156924.
  • RoHS Compliance Status: Compliant with exemption.
  • RoHS Exemption (if applicable/known): 7a, 7cI.

Input:

  • Input current: 0...20 mA, 4…20mA.
  • Input voltage: > 3 V @ 20 mA.
  • Number of inputs: 1.
  • Sensor: Current source.
  • Voltage drop, current input: 1.25 V + 0.015 Vout @25°C.

Output:

  • Cut-off frequency (-3 dB): 100 Hz.
  • Load impedance current: ≤ 600 Ω, @ max 23mA.
  • Number of outputs: 1.
  • Output current: 0...20 mA, 4 - 20 mA.
  • Type: active, connected control must be passive.

General data:

  • Accuracy: <0.1 % of measuring range.
  • Configuration: none.
  • Galvanic isolation: 2-way isolator.
  • Power consumption: 30 mW.
  • Protection degree: IP20.
  • Rail: TS 35.
  • Step response time: ≤ 5 ms.
  • Temperature coefficient: ≤ 0.01 % / °C.
  • Voltage supply: Loop powered, via 4…20 mA input.

Insulation coordination:

  • EMC standards: EN 61326-1.
  • Galvanic isolation: 2-way isolator.
  • Insulation voltage: 2.5 kVeff /1 min.
  • Pollution severity: 2.
  • Rated voltage: 300 Veff.
  • Surge voltage category: II.

Data for Ex applications (ATEX):

  • Installation location: Device installed in safe area, zone 2.
  • Marking: II 3 G Ex nA IIC T4 Gc.

Connection data:

  • Type of connection: Screw connection.
  • Tightening torque, min.: 0.4 Nm.
  • Tightening torque, max.: 0.6 Nm.
  • Clamping range, rated connection: 2.5 mm².
  • Clamping range, min.: 0.5 mm².
  • Clamping range, max.: 2.5 mm².
  • Wire connection cross section AWG, min.: AWG 30.
  • Wire connection cross section AWG, max.: AWG 14.

EMC conformity and approvals:

  • EMC standards: EN 61326-1.
  • Standards: IEC 61010-1.

Important note:

  • Product information:
    • The passive isolator ACT20M-CI-CO-ILP-S isolates standard analogue current signals.
    • An analogue input current signal is linearly converted into an analogue output current signal and is galvanically isolated.
    • Power is supplied through the input measuring circuit (input loop-powered).
More Information