ACT20X-SAI-HAO-S

ZAR 7,687.97
Out of stock
SKU
8965450000

Description:

  • Standard signals ranging from 4 to 20 mA can be sent and isolated from the safe zone to Ex zones 0, 1, and 2 using an Ex-output isolation amplifier for DC current signals. It is a transparent HART 1-channel output isolation amplifier with an external power supply and a 22.5 mm width.
  • You can access status and error messages by using a relay contact (NO).
  • The component can be set up with the help of common FDT and DTM software.
  • Extension housing for the TS35 rail installation.
  • Dimensions: L/W/H 119.2/ 22.5/ 113.6
  • Screw connection/ Nominal cross-section 2.5 mm2
  • Protection degree: IP 20 
  • Input 4...20 mA                                                                          
  • Output 4...20 mA
  • Load < 600 Ohm
  • Accuracy < 0,1 % v.E
  • Temperature coefficient < 0,01% v.E./°C (Tu)
  • Alarm output relay 1 NO contact 250 V AC / 30 V DC @ 2A safe zone, 32 V AC @ 0.5 A/ 32 VDC @ 1 A Zone 2
  • Auxiliary power 19...31.2 V DC
  • Power loss approx. 1.8 W
  • Ambient
  • temperature range -20 °C... +60 °C
  • Secure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each other
  • Working voltage 300 V AC/DC at overvoltage category II and pollution degree 2
  • Approvals cULus, ATEX IECEX, FM
  • ATEX marking II 3 G ExnA nC IIC T4
  • ATEX characteristic data U0 = 28 V DC I0 = 93 mA DC, P0 = 650 mW

Specifications:

  • Version: EX signal isolating converter, Safe-input: 4-20mA, Ex output: 4 - 20 mA, 1-channel.
  • Depth: 113.6 mm.
  • Height: 119.2 mm.
  • Width: 22.5 mm.
  • Storage temperature: -20 °C...85 °C.
  • Operating temperature: -20 °C...60 °C.
  • Humidity: 0...95 % (no condensation).
  • Mounting position: horizontal or vertical.
  • Rail: TS 35.
  • Type of mounting: Snap mounting support rail.
  • Accuracy: <0.1% span.
  • Configuration: With FDT/DTM software, Requires configuration adapter 8978580000 CBX200 USB.
  • Power consumption: ≤ 1.0 W.
  • Protection degree: IP20.
  • Step response time: ≤ 5 Ms.
  • Temperature coefficient: <0.01% of span/°C (TU).
  • Type of connection: Screw connection.
  • Voltage supply: 19.2…31.2 V DC.
  • Rated voltage: 300 V.
  • Insulation voltage: 2.6 kV (input / output).

Input:

  • Input current: 4…20mA.
  • Number of inputs: 1.
  • Voltage drops: <2 V.

Output:

  • 2-wire supply: > 14.5 V @ 20 mA.
  • Influence of load resistance: ≤ 0.01% of span / 100 Ω.
  • Load impedance current: ≤ 725 Ω.
  • Output current: 4…20 mA (max. 23 mA).
  • Output signal limit: <28 mA.
  • Residual ripple (current loop): <7.5 mV eff.
  • Type: intrinsically safe circuit.

Alarm output:

  • Alarm function: Signal limit exceeded, Line interruption at the input, No supply voltage, Device error.
  • Continuous current: ≤ 0,5 An AC / 1 A DC (zone 2).
  • Hysteresis: 0.1 mA (switching threshold).
  • Nominal switching voltage: ≤ 125 V AC / 110 V DC (safe area) ≤ 32 V AC / 32 V DC (zone 2).
  • Power rating: ≤ 62.5 VA / 32 W (safe area) ≤ 16 VA / 32 W (Zone 2).
  • Type: Status relay, 1 NC (voltage-free).