Back to Top
EK1814 EtherCAT Coupler with integrated digital inputs/outputs
The EK1814 EtherCAT Coupler is the link between the EtherCAT protocol at fieldbus level and the EtherCAT Terminals. In addition, four digital inputs and four digital outputs are integrated. The resulting design is particularly suitable for applications with a small number of I/Os. The coupler converts the passing telegrams from Ethernet 100BASE-TX to E-bus signal representation. A station consists of a coupler and any number of EtherCAT Terminals that are automatically detected and individually displayed in the process image.
Special features:
Connection technology: 2 x RJ45 socket.
Connection lengths: up to 100 m.
4 digital inputs and 4 digital outputs.
Number of EtherCAT Terminals in the overall system: up to 65535.
Task within EtherCAT system: coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCAT networks.
Data transfer medium: Ethernet/EtherCAT cable (min. Cat.5), shielded.
Distance between stations: max. 100 m (100BASE-TX)
Number of EtherCAT: Terminals up to 65,534
Protocol: EtherCAT
Delay: approx. 1 µs
Data transfer rates: 100 Mbit/s
Bus interface: 2 x RJ45
Nominal voltage: 24 V DC (-15 %/+20 %)
Current supply E-bus: 1000 mA
Current consumption from UP: 40 mA + load
Current consumption from US: 100 mA + (∑ E-bus current/4)
Number of inputs: 4
Specification: EN 61131-2, type 1/3
“0” signal voltage: -3…+5 V (EN 61131-2, type 1/3)
“1” signal voltage: 11…30 V (EN 61131-2, type 3)
Input filter: 3.0 ms
Input current: typ. 3 mA (EN 61131-2, type 3)
Number of outputs: 4
Load type: ohmic, inductive, lamp load
Max. output current: 0.5 A (short-circuit proof) per channel
Short-circuit current: typ. < 2 A
Reverse voltage protection: yes
Breaking energy: < 150 mJ/channel
Switching times: typ. TON: 60 µs, typ. TOFF: 300 µs
Electrical isolation: 500 V (power contact/supply voltage/Ethernet),500 V (E-bus/field potential)
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP20/variable
Approvals/markings: CE, UL
Write Your Own Review