Back to Top
EK3100 PROFIBUS Bus Coupler
The EK3100 Bus Coupler connects PROFIBUS networks to the EtherCAT Terminals (ELxxxx) as well as the EtherCAT Box modules (EPxxxx) and converts the telegrams from PROFIBUS to the E-bus signal representation.
Task within EtherCAT system: coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to PROFIBUS networks
Number of EtherCAT Terminals: depending on the process data size
Type/number of peripheral signals: depending on the process data size
Protocol: PROFIBUS DP
Data transfer rates: up to 12 Mbaud (automatic detection)
Configuration: not required
Bus interface: 1 x D-sub 9-pin socket with shielding
Power supply: 24 V DC (-15 %/+20 %)
Input current: typ. 120 mA + (total E-bus current)/4
Current consumption E-bus: up to 2 A
Power contacts: max. 24 V DC/max. 10 A
Electrical isolation: 500 V (power contact/supply voltage/Ethernet)
Dimensions (W x H x D): 64 mm x 100 mm x 73 mm
Operating/storage temperature: -25…+60 °C/-40…+85 °C
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.: IP20/variable
Approvals/markings: CE, UL, ATEX, IECEx
Ex marking : ATEX: II 3 G Ex nA IIC T4 Gc/IECEx: Ex ec IIC T4 Gc.
Write Your Own Review