Back to Top
EK9000 ModbusTCP/UDP Bus Coupler
The EK9000 Bus Coupler connects Ethernet networks to the EtherCAT Terminals (ELxxxx) as well as the EtherCAT Box modules (EPxxxx) and converts the telegrams from Ethernet to the E-bus signal representation.
Task within EtherCAT system: coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to Ethernet networks
Number of EtherCAT Terminals: depending on the process data size
Type/number of peripheral signals: depending on the process data size
Protocol: Modbus TCP, Modbus UDP
Data transfer rates: 100 Mbit/s
Configuration: not required
Bus interface: 2 x RJ45 (switched)
Power supply: 24 V DC (-15 %/+20 %)
Input current: typ. 120 mA + (total E-bus current)/4
Current consumption E-bus: up to 2 A
Power contacts: max. 24 V DC/max. 10 A
Electrical isolation: 500 V (power contact/supply voltage/Ethernet)
Dimensions (W x H x D): 64 mm x 100 mm x 73 mm
Operating/storage temperature: -25…+60 °C/-40…+85 °C
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.: IP20/variable
Approvals/markings: CE, UL, ATEX, IECEx
Ex marking : ATEX: II 3 G Ex nA IIC T4 Gc/ IECEx: Ex ec IIC T4 Gc
Write Your Own Review