Back to Top
EK9500 EtherNet/IP Bus Coupler
The EK9500 Bus Coupler connects EtherNet/IP networks to the EtherCAT Terminals (ELxxxx) as well as EtherCAT Box modules (EPxxxx) and converts the telegrams from EtherNet/IP to the E-bus signal representation.
Task within EtherCAT system: coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to EtherNet/IP networks
Number of EtherCAT Terminals: depending on the process data size
Type/number of peripheral signals: depending on the process data size
Protocol: EtherNet/IP
Data transfer rates: 100 Mbit/s
Configuration: not required
Bus interface: 2 x RJ45 (switched)
Power supply: 24 V DC (-15 %/+20 %)
Input current: typ. 120 mA + (total E-bus current)/4
Current consumption E-bus: up to 2 A
Power contacts: max. 24 V DC/max. 10 A
Electrical isolation: 500 V (power contact/supply voltage/Ethernet)
Dimensions (W x H x D): 64 mm x 100 mm x 73 mm
Operating/storage temperature: -25…+60 °C/-40…+85 °C
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.: IP20/see documentation
Approvals/markings: CE, UL, ATEX, IECEx
Ex marking : ATEX: II 3 G Ex nA IIC T4 Gc/ IECEx: Ex ec IIC T4 Gc