Back to Top
EL1054 EtherCAT Terminal
The EL1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal.
Technology: NAMUR
Specification: NAMUR DC switching amplifier (IEC 60947-5-6)
Signal type: binary, current input for NAMUR sensors
Number of inputs: 4
Connection technology: 2-wire
Open circuit voltage: typ. 8.2 V DC
“0” signal current: ≤ 1.2 mA
“1” signal current: ≥ 2.1 mA
Switching hysteresis: typ. 350 µA
Short-circuit current: typ. 7.8 mA
Fault detection: I ≤ 200 µA (cable break), I ≥ 7.0 mA (short circuit)
Max. switching frequency: 5 kHz (duty factor 50 %)
Internal resistance: according to I/V curve IEC 60947-5-6
Supply voltage electronics: 24 V DC (via power contacts)
Current consumption E-bus: typ. 50 mA
Electrical isolation: 500 V (E-bus/field potential)
Special features: integrated reverse polarity protection
Weight: approx. 60 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals/markings: CE, UL, ATEX, IECEx, cFMus
Ex marking: ATEX: II 3 G Ex nA IIC T4 Gc/IECEx: Ex ec IIC T4 Gc/cFMus: Class I, Division 2, Groups A, B, C, D, Class I, Zone 2, AEx ec IIC T4 Gc
Write Your Own Review