The EL2212 digital output terminal connects the binary control signals from the automation device on to the actuators at the process level with electrical isolation. The multi-timestamp features allow each EtherCAT cycle to capture as many events per channel as were preloaded in the internal buffer.
Connection technology: 4-wire
Number of outputs: 2
Nominal voltage: 24…72 V DC (-15 %/+0 %)
Load type: inductive > 1 mH
Precision of timestamp in the terminal: 10 ns
Resolution timestamp: 1 ns
Distributed clocks: yes
Distributed clock precision: << 1 µs
Max. output current: peak current: max. 10 A per channel, holding current: 0.2…2.5 A per channel
Output stage: full bridge (push-pull)
Short-circuit current: typ. 12 A
Switching times without distributed clocks: typ. TON/TOFF 20 µs, with distributed clocks: typ. TON/TOFF < 1 µs via internal compensation
Current consumption E-bus: typ. 120 mA
Electrical isolation: 500 V (E-bus/field potential)
Current consumption power contacts: load-dependent
Configuration: via TwinCAT System Manager
Special features: Multi-timestamping, current-controlled outputs can be connected in high-resistance mode.
Weight: approx. 50 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP20/variable
Pluggable wiring: for all ESxxxx terminals