EP2338-2002 EtherCAT Box
The EP2338-2002 EtherCAT Box has eight digital channels, which can each be operated as an input or output. It is not necessary to configure whether a channel (pins 2 and 4 of M12) is to be used as an input or output. The input circuit is permanently connected to the output driver internally so that a set output is also automatically displayed in the input process image.
Protocol: EtherCAT
Bus interface: 2 x M8 socket, shielded, screw type
Specification: EN 61131-2, type 1/3
Number of channels: 8 digital inputs or outputs
Input/output connections: M12, screw type
Input filter: 10 µs
“0” signal voltage: -3…+5 V
“1” signal voltage: 11…30 V, 6 mA input current (EN 61131-2, type 3)
Sensor supply: from load supply voltage, max. 0.5 A, short-circuit proof in total
Load type: ohmic, inductive, lamp load
Rated load voltage: 24 V DC (-15 %/+20 %)
Max. output current: 0.5 A per channel, individually short-circuit proof
Switching times: typ. TON: 50 µs, typ. TOFF: 100 µs
Short-circuit current: typ. 1.5 A
Auxiliary power current: typ. 20 mA + load
Current consumption from US: 120 mA
Power supply connection: feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Electrical isolation: 500 V
Weight: approx. 165 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings: CE, UL
SKU | EP2338-2002 |
---|
Write Your Own Review