Back to Top
ER3184-0002 EtherCAT Box
The ER3184-0002 EtherCAT Box has four analog inputs which can be individually parameterized, so that they process signals either in the -10/0…+10 V or the 0/4…20 mA range. The voltage or input current is digitized with a resolution of 16 bits, and is transmitted (electrically isolated) to the higher-level automation device.
Protocol: EtherCAT
Bus interface: 2 x M8 socket, shielded, screw type
Number of inputs: 4 (single-ended), 1 per socket
Input connections: M12, screw type
Signal type: -10/0…+10 V | 0/4…20 mA, parameterizable per channel
Internal resistance: > 200 kΩ | typ. 85 Ω + diode voltage
Common-mode voltage UCM: max. 35 V
Resolution: 16 bit (incl. sign)
Measuring error: < ±0.3 % (relative to full scale value)
Conversion time: ~ 100 µs
Input filter limit frequency: 5 kHz
Nominal voltage: 24 V DC (-15 %/+20 %)
Distributed clocks: yes
Input filter: configurable
Sensor supply: from load supply voltage UP
Current consumption from US: 120 mA
Power supply connection: feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Electrical isolation: 500 V
Special features: current or voltage parameterizable
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Weight: approx. 265 g
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.: IP65/66/67 (conforms to EN 60529)/variable
Approvals/markings: CE, UL
Write Your Own Review