Back to Top
EtherCAT plug-in module TwinSAFE Logic EJ1957
The EJ1957 EtherCAT plug-in module is a TwinSAFE component with inputs and outputs. The module has eight fail-safe inputs and four fail-safe outputs, which are controlled or processed via FSoE by a TwinSAFE Logic-capable component. The EJ1957 has safety parameters to specifically adapt the functionality to the respective safety requirements. For example, test pulses can be configured with fine granularity for all channels.
Connection technology: distribution board
Specification: link unit between safe input and output signals
Number of inputs: 8
Number of outputs: 4
Protocol: TwinSAFE/Safety over EtherCAT
Response time: typ. 4 ms (read input/write to E-bus)
Fault response time: ≤ watchdog time (parameterizable)
Current consumption E-bus: typ. 330 mA
Safety standard: EN ISO 13849-1: 2015 (Cat. 4, PL e) and EN 61508: 2010 (SIL 3)
Weight: approx. 64 g
Protection rating: IP20
Design form: EtherCAT I/O plug-in module
Material: polycarbonate
Installation: on signal distribution board
Mechanical coding: EJ plug-in module: signal-specific coding pins on the housing,
signal distribution board: holes in the printed circuit board
Locking: latching lug in circuit board cut-out
Connection method: field wiring: application-specific wiring level on the signal distribution board,
EJ plug-in module: 2 x 20-pin socket strip
Dimensions (W x H x D): 12 mm x 152 mm x 55 mm
Write Your Own Review