Back to Top
KBU 816 split core current transformers class 1
Current transformer split-core:
- The concept of split measuring allows for an easy installation into pre-existing panel boards without the need for additional mounting.
- To ensure that the circuit is closed, just open the current transformer's locking mechanism, place it around the primary conductor, and lock.
- The unit is ready for use after the secondary wires are attached.
General details:
- Class of isolation: E.
- Um 0.72 kV is the maximum operational voltage.
- 50 Hz is the nominal frequency (others upon request).
- Ith = 60 x In is the nominal thermal short-time current.
- FS 5 is the overcurrent limiting factor up to a notional current of 1500 A.
- The current transformers manufactured by MBS AG fully comply with DIN VDE 0414/1, DIN 42600, DIN EN 60044/1, and VBG 4.
Specifications:
- KBU 816 split core current transformers (5A secondary - class 1),
- Primary bar conductor: 80 x 160 mm max.,
- MODEL KBU 816,
- RATIO 5000/5A,
- ROUND CONDUCTOR Split core,
- PRIMARY BAR CONDUCTOR 80 x 160 mm maximum,
- DESCRIPTION Split-core current transformer,
- CLASS 1,
- VA 30,
- DIMENSIONS (MM) (H) 243 x (W) 195 x (D) 79
Brand | MBS |
---|