OFF DELAY TIMER, 180 MINUTES, 230VAC.
Delay in removing the supply (true off delay on de-energization timer):
- Installing the Electro 11 pin plug-in series of control and timing devices is simple and straightforward since they are designed to fit into a conventional 11 pin base.
- The device offers a delayed relay release upon removal of the supply.
- Internal batteries are included with time ranges of 10 to 180 minutes; however, they must be charged for 24 hours prior to use.
- To charge the internal retention circuit, power must be applied for 30% of the time range before being removed.
- Use the pulse-controlled interval timer (T2M or T1I/P) in applications where supply voltage is present.
Features:
- DPDT oscillator control time circuit with 5A output
- <1% is the repeatable deviation.
- LED power supply indicator on.
- Time setting adjustable potentiometer.
- Time interval with battery: 10–180 minutes.
- Range of time without battery: 3 to 360 seconds.
- Use PT11/PT13 for pulses less than 30 seconds plus 30%.
Specifications:
- TIME RANGE: 10min, 30min, 60min,180min
- DESCRIPTION: True off delay on de-energisation timer with battery
- CONTACT: 10A SPDT
- RATED VOLTAGE: 250V
- MECHANICAL LIFE: 10x106 cycles
- PROTECTION INDEX IP: IP 20
- OPERATING TEMPERATURE: -10 to + 50°C
- STORAGE TEMPERATURE: -50 to + 85°C
- DIMENSIONS (MM): (H) 92 x (W) 36 x (D) 64