Back to Top
Output 4 channels
Features:
- The HART protocol is supported.
- Analog signal connection allows for bi-directional digital communication in the 4–20 mA input range.
- There is no need to add wiring for HART communication if analog wiring is already being utilized (HART communication is not supported in the range of 0~20Ma).
- High-precision operation parameter monitoring and setting.
- Function for detecting disconnection of input.
Specifications:
- Number of channels: 4
- Analog input/output range: DC 4~20mA, DC 0~20Ma, (Load resistance 600Ω or less)
- Analog output/digital input: DC 4~20Ma, DC 0~20Ma
- Max. resolution: 0/64000, 4~20Ma:1.00nA:1.25nA
- Accuracy: when ambient temperature is 25°C ±5°C: ±0.10% or less
- When ambient temperature is 0°C~55°C: ±0.3% or less.
- Conversion speed: 10ms/4 channels
- Absolute max. input/output: DC 24 Ma
- Analog input points: 4 channels/ 1 module
- Isolation specification: Photo-coupler isolation between input terminal and PLC power (no isolation between channels)
- Terminal connected: 18-point terminal.
- I/O points occupied: fixed type: 64 points, non-fixed type: 16 points.
- HART communication method: Mono drop only primary master only.
- Internal-consumed current: DC 5V: 200mA, DC 24V: 220mA.
Brand | LS Electric |
---|
Write Your Own Review