Back to Top
PRO INSTA 12V 5A 60W
Switch-mode power supply unit, 12 volts:
- The single-phase INSTA-POWER switching power supplies are distinguished by their broad power spectrum, compact design, and excellent value for money.
- They can withstand temperatures ranging from -25°C to +70°C, have international approvals, and accept a wide variety of voltage input.
- They can therefore be used for a variety of purposes.
- This also covers signal and telecommunications systems, and also systems for automation with minimal power requirements of up to 96 Watts.
Specifications weights and dimensions:
- Depth: 60 mm.
- Height: 90 mm.
- Width: 72 mm.
- Net weight: 258 g.
Temperatures:
- Storage temperature range: -40°C - 85°C.
- Operating temperature range: -25°C - 70°C.
Input:
- AC current consumption: 0.7 A @ 230 V AC / 1.5 A @ 100 V AC.
- AC input voltage range: 85 - 264 V AC (derating at 100 V AC).
- Connection system: PUSH IN with actuator.
- DC current consumption: 0.25 A @ 370 V DC / 0.8 A @ 120 V DC.
- DC input voltage range: 95 - 370 V DC.
- Frequency range AC: 45 - 65 Hz.
- Input fuse (internal): Yes.
- Inrush current maximum: 40 A.
- Nominal power consumption: 69.8 VA.
- Rated input voltage: 110 - 240 V AC / 120 - 340 V DC.
- Recommended back-up fuse: 2 A / DI, safety fuse 6 A, Char. B, circuit breaker 2 - 4 A, Char. C circuit breaker.
- Wire connection method: PUSH IN with actuator.
Output:
- Capacitive load: unrestricted.
- Connection system: PUSH IN.
- Continuous output current @ UNominal: 5 A @ 55 °C, 3.75 A @ 70 °C.
- Nominal output current for Unom: 5 A @ 55 °C.
- Output current, maximum: 5 A.
- Output power: 60 W.
- Output voltage, maximum: 16 V.
- Output voltage, minimum: 9 V.
- Output voltage, note: (adjustable via potentiometer on front).
- Ramp-up time: ≤ 100 ms.
- Rated output voltage: 12 V DC ± 1 %.
- Residual ripple, breaking spikes: < 50 mVss @ UNenn, Full Load.
- Wire connection method: PUSH IN with actuator.
General data:
- Degree of efficiency: 86%.
- Housing version: Plastic, protective insulation.
- Mounting position, installation notice: Horizontal on DIN rail TS 35, top and bottom 50 mm clearance for free air flow, 10 mm clearance to neighbouring active subassemblies with full load, 5 mm with passive neighbouring subassemblies, direct row mounting with 90% rated load.
- MTBF:
- According to Standard: Telcordia SR-332.
- Operating time (hours), minimum: 792,000 h.
- Ambient temperature: 25 °C.
- Input voltage: 230 V.
- Output power: 60 W.
- Duty cycle: 100 %.
- According to Standard: Telcordia SR-332.
- Operating time (hours), minimum: 376,000 h.
- Ambient temperature: 40 °C.
- Input voltage: 230 V.
- Output power: 60 W.
- Duty cycle: 100 %.
- Power loss, idling: 0.42 W.
- Power loss, nominal load: 8.4 W.
- Protection against reverse voltages from the load: 18 - 25 V DC.
- Protection degree: IP20.
- Short-circuit protection: Yes, internal.
- Start-up: ≥ -40 °C.
EMC / shock / vibration:
- Interference immunity test according to: EN 61000-4-2 (ESD)| EN 61000-4-3 and EN 61000-4-8 (fields)| EN 61000-4-4 (burst)| EN 61000-4-5 (surge)| EN 61000-4-6 (conducted)| EN 61000-4-11 (dips) EN 61000-4-11 (Dips).
- Limiting of mains voltage harmonic currents: EN 61000-4-2 (ESD)|EN 61000-4-3 and EN 61000-4-8 (fields)| EN 61000-4-4 (burst)| EN 61000-4-5 (surge)| EN 61000-4-6 (conducted)| EN 61000-4-11 (dips) EN 61000-4-11 (Dips).
- Noise emission in accordance with EN55032: Class B.
- Shock resistance IEC 60068-2-27: 15 g in all directions.
- Vibration resistance IEC 60068-2-6: 2.3 g.
Insulation coordination:
- Insulation voltage input / earth: 3.5 kV.
- Insulation voltage output / earth: 0.5 kV.
- Insulation voltage, input/output: 4 kV.
- Pollution severity: 2.
- Protection class: II.
Electrical safety (applied standards):
- Electrical machine equipment: According to EN60204.
- For use with electronic equipment: According to EN50178 / VDE0160.
- Protection against dangerous shock currents: According to VDE0106-101.
- Protective separation / protection against electrical shock: VDE0100-410 / according to DIN57100-410.
- Safety extra-low voltage: SELV acc. to IEC 60950-1, PELV according to EN 60204-1.
- Safety transformers for switch-mode power supplies: According to EN 61558-2-16.
Connection data (input):
- Conductor cross-section, AWG/kcmil, maximum: 12.
- Conductor cross-section, AWG/kcmil, minimum: 24.
- Conductor cross-section, flexible, minimum: 0.25 mm².
- Conductor cross-section, rigid, maximum: 2.5 mm².
- Conductor cross-section, rigid, minimum: 0.25 mm².
- Connection system: PUSH IN with actuator.
- Number of terminals: 2 (L, N).
- Wire connection cross section, flexible (input), max.: 2.5 mm².
Connection data (output):
- Conductor cross-section, AWG/kcmil, maximum: 12.
- Conductor cross-section, AWG/kcmil, minimum: 24.
- Conductor cross-section, flexible, maximum: 2.5 mm².
- Conductor cross-section, flexible, minimum: 0.25 mm².
- Conductor cross-section, rigid, maximum: 2.5 mm².
- Conductor cross-section, rigid, minimum: 0.25 mm².
- Connection system: PUSH IN.
- Number of terminals: 4 (++ / --).
Signalling:
- LED green: Operating voltage OK.
Approbations:
- Certificate no. (cULus): E258476.
- Institute (cULus): CULUS.
Brand | Weidmuller |
---|
Write Your Own Review