Back to Top
Rnet Master
Rnet Master Communication unit:
- Data Processing unit: Byte
- Tx/Rx cycle: Selection among 20ms, 50ms, 100ms, 200ms(default), 500ms, 1s, 5s, 10s
- Max. Communication points: 3,780 Bytes (slave 31stations * 120Bytes/station)
- Max. Block number: 64 (setting range: 0~63)
- Max. points by Block: 120 Byte (60words)
- Auto scanning: Supported
Specifications:
- Transmission speed: 1Mbps (Rnet I/F modules common)
- Max. Tx distance: 750m
- Connection Cable: Twisted pair shielded cable
- Maximum stations connected (Network): Master station 1[station no:0(fixed)] and Slave stations up to 31[station no:1~63) Only 1 master is available in the network.
- Diagnostic function: XG5000: High Speed Link Monitoring
- Terminal resistance (Ω): 110 Ω (±5%), 1/2W
- Master/Slave operation: Only available as Master
- Max. module mounted: 2 modules.
Brand | LS Electric |
---|
Write Your Own Review
Write your content here...