Back to Top
Siemens S7-1500 SIMATIC PM 1507 Load Power Supply 24 V DC/8A
Pricing available on request
Description:
- SIMATIC PM1507-1AC/24VDC/8A.
- SIMATIC PM 1507: 24 V/8 A regulated power supply for SIMATIC S7-1500.
- Input voltage: 120/230 V AC, output current: 24 V DC/8 A.
Input:
- type of the power supply network: 1-phase AC.
- supply voltage at AC: Automatic range selection.
- supply voltage: 120 V/230 V.
- input voltage 1 at AC: 85 ... 132 V.
- input voltage 2 at AC: 170 ... 264 V.
- wide range input: No.
- overvoltage overload capability: 2.3 × Vin rated, 1.3 ms.
- buffering time for rated value of the output current in the event of power failure minimum: 20 ms.
- operating condition of the mains buffering: at Vin = 93/187 V.
- line frequency: 50/60 Hz.
- line frequency: 45 ... 65 Hz.
- input current:
- at rated input voltage 120 V: 3.7 A.
- at rated input voltage 230 V: 1.7 A.
- current limitation of inrush current at 25 °C maximum: 62 A.
- duration of inrush current limiting at 25 °C:
- maximum: 3 ms.
- I2t value maximum: 12 A²·s.
- fuse protection type: T 6.3,15 A/250 V (not accessible).
- fuse protection type in the feeder: Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C.
Output:
- voltage curve at output: Controlled, isolated DC voltage.
- output voltage at DC rated value: 24 V.
- output voltage:
- at output 1 at DC rated value: 24 V.
- output voltage adjustable: No.
- relative overall tolerance of the voltage: 1 %.
- relative control precision of the output voltage.
- on slow fluctuation of input voltage: 0.1 %.
- on slow fluctuation of ohm loading: 0.1 %.
- residual ripple:
- maximum: 50 mV.
- voltage peak:
- maximum: 150 mV.
- display version for normal operation: LED green for 24 V OK; LED red for error; LED yellow for stand-by.
- behavior of the output voltage when switching on: No overshoot of Vout (soft start).
- response delay maximum: 1.5 s.
- voltage increase time of the output voltage:
- typical: 10 ms.
- output current:
- rated value: 8 A.
- rated range: 0 ... 8 A.
- supplied active power typical: 192 W.
- short-term overload current:
- on short-circuiting during the start-up typical: 35 A.
- at short-circuit during operation typical: 35 A.
- duration of overloading capability for excess current:
- on short-circuiting during the start-up: 70 ms.
- at short-circuit during operation: 70 ms.
- bridging of equipment: Yes.
- number of parallel-switched equipment resources for increasing the power: 2.
efficiency:
- efficiency in percent: 90 %.
- power loss [W]:
- at rated output voltage for rated value of the output current typical: 21 W.
SKU | 6EP1333-4BA00 |
---|---|
Brand | Siemens |
Write Your Own Review