Back to Top
UR20-4AI-UI-12
UR20-4AI-UI-12:
- Analogue input modules for the u-remote system are available in a variety of resolutions and wiring options.
- A number of variants with 12- and 16-bit resolution that can record as accurately as possible up to 4 analogue sensors with +/-10 V, +/-5 V, 0...10 V, 0...5 V, 2...10 V, 1...5 V, 0...20 mA, or 4...20 mA.
- Plug-in connectors can link sensors with either 2- or 3-wire technology.
- The measurement range settings can be modified individually for each channel.
- Every channel also has a unique status LED.
- A specific variation for Weidmüller interface devices allows current measurements with 16-bit resolution and maximum precision for 8 sensors at once (0...20 mA or 4...20 mA).
Specification dimensions and weights:
- Depth: 76 mm.
- Depth (inches): 2.992 inch.
- Height: 120 mm.
- Height (inches): 4.724 inch.
- Width: 11.5 mm.
- Width (inches): 0.453 inch.
- Mounting dimension - height: 128 mm.
- Net weight: 87 g.
Temperatures:
- Storage temperature: -40 °C - +85 °C.
- Operating temperature: -20 °C - +60 °C.
Environmental Product Compliance:
- REACH SVHC: Lead 7439-92-1.
- SCIP: 82327f13-cd27-455a-ab5b-a62e1996dcf8.
analogue inputs:
- Accuracy: 0.1% FSR.
- Conversion time: 1 ms.
- Individual channel diagnosis: No.
- Internal resistance I: 41.2 Ω.
- Internal resistance U: 100 kΩ.
- Module diagnosis: Yes.
- Number of analogue inputs: 4.
- Resolution: 12-bit.
- Response time: < 50 ms.
- Reverse polarity protection: Yes.
- Sensor connection: 2-wire.
- 3-wire.
- 3-wire + FE.
- Sensor supply: Yes.
- Sensor supply:
- minimum: 0 mA.
- nominal: 750 mA.
- maximum: 750 mA.
- Short-circuit-proof: Yes.
- Type:
- 1. U (0…5 V, 0…10 V, 1…5 V, 2…10 V, ±10 V).
- 2. I (0–20 mA or 4–20 mA).
- Adjustable input for current or voltage.
Connection data:
- Type of connection: PUSH IN.
- Wire connection cross section, finely stranded, maximum: 1.5 mm².
- Wire connection cross section, finely stranded, minimum: 0.14 mm².
- Wire cross-section, finely stranded, maximum (AWG): AWG 16.
- Wire cross-section, finely stranded, minimum (AWG): AWG 26.
- Wire cross-section, solid, maximum: 1.5 mm².
- Wire cross-section, solid, maximum (AWG): AWG 16.
- Wire cross-section, solid, minimum: 0.14 mm².
- Wire cross-section, solid, minimum (AWG): AWG 26.
General data:
- Air humidity (operation): 10% to 95%, non-condensing as per DIN EN 61131-2.
- Air humidity (storage): 10% to 95%, non-condensing as per DIN EN 61131-2.
- Air humidity (transport): 10% to 95%, non-condensing as per DIN EN 61131-2.
- Air pressure (operation): ≥ 795 hPa (height ≤ 2000 m) as per DIN EN 61131-2.
- Air pressure (storage): 1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2.
- Air pressure (transport): 1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2.
- Pollution severity: 2.
- Rail: TS 35.
- Shock: 15 g over 11 ms, half sinus wave, acc.to IEC 60068-2-27.
- Surge voltage category: II.
- Test voltage: 500 V.
- UL 94 flammability rating: V-0.
- Vibration resistance: 5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6, 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration as per IEC 60068-2-6.
Power supply:
- Current consumption from IIN (the respective power segment): 25 mA + sensor feed.
- Current consumption from Isys, typ.: 8 mA.
- Reverse polarity protection: Yes.
- Voltage supply: 24 V DC +20 %/ -15 % via the system bus.
System data:
- Diagnostic data: 1 Bit.
- Field bus protocol: PROFINET IRT, PROFINET RT, CC-Link IE TSN, IEC 61162-450, PROFIBUS DP-V1, EtherCAT, Modbus/TCP, EtherNet/IP, CANopen, DeviceNet, POWERLINK, CC-Link.
- Galvanic isolation: 500 V DC between the current paths.
- Interface: u-remote system bus.
- Module type: Analogue input module.
- Parameter data: 14 Byte.
- Process data: 8 Byte.
- Transmission speed of system bus, maximum: 48 Mbit.
Brand | Weidmuller |
---|