VSPC 4SL 24VDC EX

ZAR 7,036.97
Out of stock
SKU
1161190000

VSPC 4SL 24VDC EX:

  • Binary signals (SL - Symmetrical Load) protection covers the following signals:
  • switching signals between a common reference potential, such as 5 V, 24 V, and 60 V, and one without.
  • Two-conductor systems typically use a shared reference potential for binary sensors, actuators, and indicators such as limit switches, buttons, position sensors, photoelectric barriers, contactors, solenoid valves, indicator lamps, and so on.
  • For interruption-free and impedance-neutral plug-in and pull-out, use a pluggable arrester.
  • able to be examined using the V-TEST testing apparatus.
  • Version with floating-earth PE connection used to avoid interference currents caused by potential differences.
  • For use in accordance with IEC 62305 and IEC61643-22 installation requirements (D1, C1, C2, and C3).
  • A safe discharge of up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to the PE is possible with an integrated PE foot.
  • Voltage levels are colour-coded for easy identification on the panel.
  • By using coding elements at various voltage levels, safety is provided.

Dimensions and weights:

  • Depth: 69 mm.
  • Depth (inches): 2.717 inch.
  • Height: 90 mm.
  • Height (inches): 3.543 inch.
  • Width: 17.8 mm.
  • Width (inches): 0.701 inch.
  • Net weight: 51 g.

Temperatures:

  • Storage temperature: -40 °C - 80 °C.
  • Operating temperature: -40 °C - 70 °C.
  • Humidity: 5 - 96 %.

Probability of failure:

  • SIL in compliance with IEC 61508: 2.
  • MTTF: 2,665 a.
  • SFF: 79.3 %.
  • λges: 43.
  • PFH in 1*10-9 per hour: 8.9.

Environmental Product Compliance:

  • REACH SVHC: Lead 7439-92-1.
  • SCIP: 71e97bb7-979f-4330-94c0-20c629bb05e3.

Protection Ex – Data:

  • ATEX - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
  • ATEX - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
  • Certificate No. (ATEX): KEMA10ATEX0148X.
  • IECEx - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
  • IECEx - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
  • Input power, max. PI: 3 W.
  • Input voltage, max. Ui: 26 V.
  • Internal capacity, max. CI: < 4 nF.
  • Internal inductance, max. LI: 0 µH.
  • Temperature class T4/135°C (-40°C  -  +85°C) li: 350 mA.
  • Temperature class T5/100°C (-40 ° C  -  +75°C) li: 250 mA.
  • Temperature class T6/85 °C (-40 °C  -  +60°C) li: 250 mA.

Rated data UL:

  • UL certificate: UL 497b Certificate.
  • CSA protection data:
  • Gas group C: IIB.
  • Gas group D: IIA.
  • Gas groups A, B: IIC.
  • Input voltage, max. Ui: 26 V.
  • Internal capacity, max. CI: 4 nF.
  • Internal inductance, max. LI: 0 µH.

General data:

  • Colour: Light Blue.
  • Design: Terminal, miscellaneous.
  • Optical function display: No.
  • protected binary signals: 4.
  • Protection degree: IP20.
  • Segment: Measurement - Monitoring - Setting.
  • UL 94 flammability rating: V-0.
  • Version: without warning function / function indicator.
  • Insulation coordination acc. to EN 50178:
  • Pollution severity: 2.
  • Surge voltage category: III.

Rated data IEC / EN:

  • Dielectric strength at FG against PE: ≥ 500 V.
  • Discharge current Imax (8/20µs) GND-PE: 10 kA.
  • Discharge current Imax (8/20µs) wire-PE: 10 kA.
  • Discharge current Imax (8/20µs) wire-wire: 10 kA.
  • Discharge current In (8/20µs) GND-PE: 2.5 kA.
  • Discharge current In (8/20µs) wire-PE: 2.5 kA.
  • Discharge current In (8/20µs) wire-wire: 2.5 kA.
  • Input voltage, max. Ui: 26 V.
  • Lightning test current, Iimp (10/350 µs) GND-PE: 2.5 kA.
  • Lightning test current, Iimp (10/350 µs) Wire-PE: 2.5 kA.
  • Lightning test current, Iimp (10/350 µs) wire-wire: 2.5 kA.
  • Max. continuous voltage, Uc (DC): 26 V.
  • Number of poles: 2.
  • Overload - failure mode: Modus 2.
  • Protection level on output side Wire-PE 1kV/µs, typically: 40 V.
  • Protection level on output side Wire-wire 1 kV/µs, typically: 80 V.
  • Protection level on output side Wire-wire 8/20 µs, typically: 80 V.
  • Protection level UP (typ.): 250 V.
  • Protection level, UP GND - PE: 60 V.
  • Protection level, UP wire - PE: 60 V.
  • Protection level, UP wire - wire: 80 V.
  • Pulse-reset capacity: ≤ 30 ms.
  • Rated current IN: 300 mA.
  • Rated voltage (DC): 24 V.
  • Requirements category acc. to IEC 61643-21: C1, C2, C3, D1.
  • Signal transmission properties (-3 dB): 4 MHz.
  • Signalling contact: No.
  • Standards: IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006.
  • Surge current-carrying capacity C1: < 1 kA 8/20 μs.
  • Surge current-carrying capacity C2: 5 kA 8/20 μs.
  • Surge current-carrying capacity C3: 100 A 10/1000 μs.
  • Surge current-carrying capacity D1: 2.5 kA 10/350 μs.
  • Voltage type: DC.
  • Volume resistance: 4.7 Ω.

Further details of approvals:

  • GOST certificate: GOST-Zertifikat.

Connection data:

  • Type of connection: Pluggable in VSPC BASE.

Ratings IECEx/ATEX/cUL:

  • ATEX - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
  • ATEX - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
  • ATEX certificate: ATEX Certificate.
  • Certificate No. (ATEX): KEMA10ATEX0148X.
  • IEC Ex certificate: IECEX Zertifikat.
  • IECEx - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
  • IECEx - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
  • cUL certificate: cUL Certificate.

Important note:

  • Product information:
    • Mode 2:
      • State where the voltage-limiting part of the SPD was short-circuited due to a very low impedance within the SPD.
      • The line is inoperable, but the measuring equipment is still protected by means of a short-circuit.