Back to Top
VSPC 4SL 24VDC EX
VSPC 4SL 24VDC EX:
- Binary signals (SL - Symmetrical Load) protection covers the following signals:
- switching signals between a common reference potential, such as 5 V, 24 V, and 60 V, and one without.
- Two-conductor systems typically use a shared reference potential for binary sensors, actuators, and indicators such as limit switches, buttons, position sensors, photoelectric barriers, contactors, solenoid valves, indicator lamps, and so on.
- For interruption-free and impedance-neutral plug-in and pull-out, use a pluggable arrester.
- able to be examined using the V-TEST testing apparatus.
- Version with floating-earth PE connection used to avoid interference currents caused by potential differences.
- For use in accordance with IEC 62305 and IEC61643-22 installation requirements (D1, C1, C2, and C3).
- A safe discharge of up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to the PE is possible with an integrated PE foot.
- Voltage levels are colour-coded for easy identification on the panel.
- By using coding elements at various voltage levels, safety is provided.
Dimensions and weights:
- Depth: 69 mm.
- Depth (inches): 2.717 inch.
- Height: 90 mm.
- Height (inches): 3.543 inch.
- Width: 17.8 mm.
- Width (inches): 0.701 inch.
- Net weight: 51 g.
Temperatures:
- Storage temperature: -40 °C - 80 °C.
- Operating temperature: -40 °C - 70 °C.
- Humidity: 5 - 96 %.
Probability of failure:
- SIL in compliance with IEC 61508: 2.
- MTTF: 2,665 a.
- SFF: 79.3 %.
- λges: 43.
- PFH in 1*10-9 per hour: 8.9.
Environmental Product Compliance:
- REACH SVHC: Lead 7439-92-1.
- SCIP: 71e97bb7-979f-4330-94c0-20c629bb05e3.
Protection Ex – Data:
- ATEX - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- ATEX - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- Certificate No. (ATEX): KEMA10ATEX0148X.
- IECEx - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- IECEx - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- Input power, max. PI: 3 W.
- Input voltage, max. Ui: 26 V.
- Internal capacity, max. CI: < 4 nF.
- Internal inductance, max. LI: 0 µH.
- Temperature class T4/135°C (-40°C - +85°C) li: 350 mA.
- Temperature class T5/100°C (-40 ° C - +75°C) li: 250 mA.
- Temperature class T6/85 °C (-40 °C - +60°C) li: 250 mA.
Rated data UL:
- UL certificate: UL 497b Certificate.
- CSA protection data:
- Gas group C: IIB.
- Gas group D: IIA.
- Gas groups A, B: IIC.
- Input voltage, max. Ui: 26 V.
- Internal capacity, max. CI: 4 nF.
- Internal inductance, max. LI: 0 µH.
General data:
- Colour: Light Blue.
- Design: Terminal, miscellaneous.
- Optical function display: No.
- protected binary signals: 4.
- Protection degree: IP20.
- Segment: Measurement - Monitoring - Setting.
- UL 94 flammability rating: V-0.
- Version: without warning function / function indicator.
- Insulation coordination acc. to EN 50178:
- Pollution severity: 2.
- Surge voltage category: III.
Rated data IEC / EN:
- Dielectric strength at FG against PE: ≥ 500 V.
- Discharge current Imax (8/20µs) GND-PE: 10 kA.
- Discharge current Imax (8/20µs) wire-PE: 10 kA.
- Discharge current Imax (8/20µs) wire-wire: 10 kA.
- Discharge current In (8/20µs) GND-PE: 2.5 kA.
- Discharge current In (8/20µs) wire-PE: 2.5 kA.
- Discharge current In (8/20µs) wire-wire: 2.5 kA.
- Input voltage, max. Ui: 26 V.
- Lightning test current, Iimp (10/350 µs) GND-PE: 2.5 kA.
- Lightning test current, Iimp (10/350 µs) Wire-PE: 2.5 kA.
- Lightning test current, Iimp (10/350 µs) wire-wire: 2.5 kA.
- Max. continuous voltage, Uc (DC): 26 V.
- Number of poles: 2.
- Overload - failure mode: Modus 2.
- Protection level on output side Wire-PE 1kV/µs, typically: 40 V.
- Protection level on output side Wire-wire 1 kV/µs, typically: 80 V.
- Protection level on output side Wire-wire 8/20 µs, typically: 80 V.
- Protection level UP (typ.): 250 V.
- Protection level, UP GND - PE: 60 V.
- Protection level, UP wire - PE: 60 V.
- Protection level, UP wire - wire: 80 V.
- Pulse-reset capacity: ≤ 30 ms.
- Rated current IN: 300 mA.
- Rated voltage (DC): 24 V.
- Requirements category acc. to IEC 61643-21: C1, C2, C3, D1.
- Signal transmission properties (-3 dB): 4 MHz.
- Signalling contact: No.
- Standards: IEC 61643-21, IEC 62305, DIN EN 60079-0.2009, DIN EN 60079-11:2007, DIN EN 60079-26:2007, DIN EN 61241-11:2006.
- Surge current-carrying capacity C1: < 1 kA 8/20 μs.
- Surge current-carrying capacity C2: 5 kA 8/20 μs.
- Surge current-carrying capacity C3: 100 A 10/1000 μs.
- Surge current-carrying capacity D1: 2.5 kA 10/350 μs.
- Voltage type: DC.
- Volume resistance: 4.7 Ω.
Further details of approvals:
- GOST certificate: GOST-Zertifikat.
Connection data:
- Type of connection: Pluggable in VSPC BASE.
Ratings IECEx/ATEX/cUL:
- ATEX - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- ATEX - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- ATEX certificate: ATEX Certificate.
- Certificate No. (ATEX): KEMA10ATEX0148X.
- IEC Ex certificate: IECEX Zertifikat.
- IECEx - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- IECEx - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- cUL certificate: cUL Certificate.
Important note:
- Product information:
- Mode 2:
- State where the voltage-limiting part of the SPD was short-circuited due to a very low impedance within the SPD.
- The line is inoperable, but the measuring equipment is still protected by means of a short-circuit.