Back to Top
VSSC6 RTD EX
VSSC6 RTD EX:
- Overvoltage coupling along the conductor path might impair or destroy sensitive signal inputs.
- It is critical to offer security in the immediate proximity of I&C equipment.
- Weidmüller's extensive product line for the I&C industry includes 2-piece, pluggable designs as well as modular terminals for tension clamp or screw connections.
- These items are compatible with both binary and analogue signals.
- Weidmüller also provides additional designs with integrated components like gas discharge tubes and varistors.
- Variator is an abbreviation for Weidmüller's flexible and variable surge protection, which is tested in compliance with product standard IEC61643-21.
- The VARITECTOR series is suitable for applications in IEC 61643-22 / VDE 0845-3 classes C1, C2, C3, and D1.
- The VARITECTOR SPC, SSC, and MCZ OVP product families effectively integrate electrical and mechanical qualities.
- Size and ease of handling are crucial considerations.
- In industrial and process automation applications as well as building automation, this surge prevention is appropriate for cramped areas.
Dimensions and weights:
- Depth: 81 mm.
- Depth (inches): 3.189 inch.
- Height: 88.5 mm.
- Height (inches): 3.484 inch.
- Width: 12.4 mm.
- Width (inches): 0.488 inch.
- Net weight: 56.8 g.
Temperatures:
- Storage temperature: -40 °C - 80 °C.
- Operating temperature: -40 °C - 70.
- Humidity: 5 - 96 %.
Probability of failure:
- SIL in compliance with IEC 61508: 3.
- MTTF: 1,871 a.
- SFF: 94.67 %.
- λges: 61.
- PFH in 1*10-9 per hour: 3.25.
Environmental Product Compliance:
- REACH SVHC: Lead 7439-92-1.
- SCIP: 71e97bb7-979f-4330-94c0-20c629bb05e3.
Protection Ex – Data:
- ATEX - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- ATEX - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- IECEx - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- IECEx - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- Input power, max. PI: 0.75 W.
- Input voltage, max. Ui: 5 V.
- Internal capacity, max. CI: 7 nF.
- Internal inductance, max. LI: 0 µH.
- Temperature class T4/135°C (-40°C - +120 °C) li: 300 mA.
- Temperature class T5/100°C (-40 ° C - +85 °C) li: 300 mA.
- Temperature class T6/85 °C (-40 °C - +70 °C) li: 300 mA.
CSA protection data:
- Gas group C: IIB.
- Gas group D: IIA.
- Gas groups A, B: IIC.
- Input current, max. II: 300 mA.
- Input voltage, max. Ui: 5 V.
- Internal capacity, max. CI: 7 nF.
- Internal inductance, max. LI: 0 µH.
General data:
- Colour: Light Blue.
- Design: Terminal.
- Isolating function: No.
- Optical function display: No.
- Protection degree: IP20.
- Rail: TS 35.
- Segment: Measurement - Monitoring - Setting.
- UL 94 flammability rating: V-0.
- Version: Surge protection for measurement and control.
Insulation coordination acc. to EN 50178:
- Pollution severity: 2.
- Surge voltage category: III.
Rated data IEC / EN:
- Dielectric strength at FG against PE: ≥ 500 V.
- Discharge current Imax (8/20µs) wire-PE: 5 kA.
- Discharge current Imax (8/20µs) wire-wire: 5 kA.
- Discharge current In (8/20µs) wire-PE: 2.5 kA.
- Discharge current In (8/20µs) wire-wire: 2.5 kA.
- Discharge current, max. (8/20 µs): 10 kA.
- Input voltage, max. Ui: 5 V.
- Insertion loss: 119.64 MHz.
- Lightning test current Iimp (10/350 µs): 0.5 kA.
- Lightning test current, Iimp (10/350 µs) Wire-PE: 0.5 kA.
- Max. continuous voltage, Uc (DC): 5 V.
- Overload - failure mode: Modus 2.
- Protection level UP (typ.): ≤ 1.8 kV.
- Protection level, UP wire - wire: 15 V
- Pulse-reset capacity: ≤ 10 ms.
- Rated current IN: 300 mA.
- Rated voltage (DC): 1 V.
- Requirements category acc. to IEC 61643-21: C2, D1.
- Signal transmission properties (-3 dB): 120 Mhz.
- Standards: IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-26:2007, DIN EN 61241-11:2006.
- Surge current-carrying capacity C2: 2.5 kA 8/20 µs 5 kV 1.2/50 µs.
- Surge current-carrying capacity C3: 10 A 10/1000 µs.
- Surge current-carrying capacity D1: 0.5 kA 10/350 μs.
- Voltage type: DC.
- Volume resistance: 1.8 Ω 10 %.
Further details of approvals:
- GOST certificate: GOST-Zertifikat.
Connection data:
- Type of connection: Screw connection.
- Tightening torque, min.: 0.5 Nm.
- Tightening torque, max.: 0.8 Nm
- Clamping range, min.: 0.5 mm².
- Clamping range, max.: 4 mm².
- Wire cross-section, solid, min.: 0.5 mm².
- Wire cross-section, solid, max.: 6 mm².
- Conductor cross-section, flexible, AEH (DIN 46228-1), min.: 0.5 mm².
- Conductor cross-section, flexible, AEH (DIN 46228-1), max.: 4 mm².
- Connection cross-section, stranded, min.: 0.5 mm².
- Connection cross-section, stranded, max.: 4 mm².
Ratings IECEx/ATEX/cUL:
- ATEX - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- ATEX - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- ATEX certificate: ATEX Certificate.
- IEC Ex certificate: IECEX Zertifikat.
- IECEx - dust labelling: II 1 D Ex ia IIIC T135 °C …T85 °C Da.
- IECEx - gas labelling: II 1 G Ex ia IIC T4… T6 Ga.
- cUL certificate: cUL Certificate.
Important note:
- Product information:
- Mode 2:
- State where the voltage-limiting part of the SPD was short-circuited due to a very low impedance within the SPD.
- The line is inoperable, but the measuring equipment is still protected by means of a short-circuit.
Brand | Weidmuller |
---|