VSSC6 RTD:

  • Overvoltage coupling along the conductor path might impair or destroy sensitive signal inputs.
  • It is critical to offer security in the immediate proximity of I&C equipment.
  • Weidmüller's extensive product line for the I&C industry includes 2-piece, pluggable designs as well as modular terminals for tension clamp or screw connections.
  • These items are compatible with both binary and analogue signals.
  • Weidmüller also provides additional designs with integrated components like gas discharge tubes and varistors.
  • Variator is an abbreviation for Weidmüller's flexible and variable surge protection, which is tested in compliance with product standard IEC61643-21.
  • The VARITECTOR series is suitable for applications in IEC 61643-22 / VDE 0845-3 classes C1, C2, C3, and D1.
  • The VARITECTOR SPC, SSC, and MCZ OVP product families effectively integrate electrical and mechanical qualities.
  • Size and ease of handling are crucial considerations.
  • In industrial and process automation applications as well as building automation, this surge prevention is appropriate for cramped areas.

Dimensions and weights:

  • Depth: 81 mm.
  • Depth (inches): 3.189 inch.
  • Height: 88.5 mm.
  • Height (inches): 3.484 inch.
  • Width: 6.2 mm.
  • Width (inches): 0.244 inch.
  • Net weight: 43.8 g.

Temperatures:

  • Storage temperature: -40 °C - 80 °C.
  • Operating temperature: -40 °C - 70.
  • Humidity: 5 - 96 %.

Probability of failure:

  • SIL in compliance with IEC 61508: 3.
  • MTTF: 1,812 a.
  • SFF: 94.05 %.
  • λges: 63.
  • PFH in 1*10-9 per hour: 3.75.

Environmental Product Compliance:

  • REACH SVHC: Lead 7439-92-1.
  • SCIP: 71e97bb7-979f-4330-94c0-20c629bb05e3.

Rated data UL:

  • Certificate No. (UL): E311081.
  • CSA protection data:

    • Gas group C: IIB.
    • Gas group D: IIA.
    • Gas groups A, B: IIC.
    • Input current, max. II: 300 mA.
    • Input voltage, max. Ui: 5 V.
    • Internal capacity, max. CI: 9 nF.
    • Internal inductance, max. LI: 0 µH.

    General data:

    • Colour: Black.
    • Design: Terminal.
    • Optical function display: No.
    • Protection degree: IP20.
    • Rail: TS 35.
    • Segment: Measurement - Monitoring - Setting.
    • UL 94 flammability rating: V-0.
    • Version: Surge protection for measurement and control.

    Insulation coordination acc. to EN 50178:

    • Pollution severity: 2.
    • Surge voltage category: III.

    Rated data IEC / EN:

    • Discharge current Imax (8/20µs) wire-PE: 5 kA.
    • Discharge current Imax (8/20µs) wire-wire: 5 kA.
    • Discharge current In (8/20µs) wire-PE: 2.5 kA.
    • Discharge current In (8/20µs) wire-wire: 2.5 kA.
    • Discharge current, max. (8/20 µs): 10 kA.
    • Insertion loss: 117.08 MHz.
    • Lightning test current Iimp (10/350 µs): 0.5 kA.
    • Max. continuous voltage, Uc (DC): 5 V.
    • Number of poles: 1.
    • Overload - failure mode: Modus 2.
    • Protection level UP (typ.): 150 V.
    • Protection level, UP wire - wire: 15 V
    • Pulse-reset capacity: ≤ 10 ms.
    • Rated current IN: 300 mA.
    • Rated voltage (DC): 1 V.
    • Requirements category acc. to IEC 61643-21: C2, D1.
    • Surge current-carrying capacity C2: 2.5 kA 8/20 µs 5 kV 1.2/50 µs.
    • Surge current-carrying capacity C3: 10 A 10/1000 µs.
    • Surge current-carrying capacity D1: 0.5 kA 10/350 μs.
    • Voltage type: DC.
    • Volume resistance: 1.8 Ω 10 %.

    Further details of approvals:

    • GOST certificate: GOST-Zertifikat.

    Connection data:

    • Stripping length: 10 mm.
    • Type of connection: Screw connection.
    • Tightening torque, min.: 0.5 Nm.
    • Tightening torque, max.: 0.8 Nm
    • Clamping range, min.: 0.5 mm².
    • Clamping range, max.: 4 mm².
    • Wire cross-section, solid, min.: 0.5 mm².
    • Wire cross-section, solid, max.: 6 mm².
    • Conductor cross-section, flexible, AEH (DIN 46228-1), min.: 0.5 mm².
    • Conductor cross-section, flexible, AEH (DIN 46228-1), max.: 4 mm².
    • Connection cross-section, stranded, min.: 0.5 mm².
    • Connection cross-section, stranded, max.: 4 mm².

    Ratings IECEx/ATEX/cUL:

    • cUL certificate: cUL Certificate.

    Important note:

    • Product information:
      • Mode 2:
        • State where the voltage-limiting part of the SPD was short-circuited due to a very low impedance within the SPD.
        • The line is inoperable, but the measuring equipment is still protected by means of a short-circuit.