AI Assistant
Cart
Quote
ControlLogix 8 Pt A/O HART Iso Module
SKU: 1756-OF8IHK
Out of stock
Availability: Out of Stock
Marketplace sellers
Submit a quote request to receive offers from sellers of this product.
Short Description
Description:
The 1756-OF8IHK is an advanced 8-channel analogue output module for ControlLogix systems that integrates high-precision current output, HART connectivity, and individual channel isolation.
It's designed for harsh industrial conditions, with conformal coating that protects against moisture, dust, and corrosive substances.
Each channel has 4-20 mA or 0-20 mA output and a dedicated HART modem for simultaneous analogue control and digital communication with smart field equipment such as transmitters and valves.
This dual-layer capability allows for real-time diagnostics, remote configuration, and increased asset management—all without the need for additional wiring.
Whether you're controlling a chemical plant, refining oil, or managing water treatment, the 1756-OF8IHK provides reliable performance, versatility, and intelligent connection in a single compact module.
8 isolated analogue output channels. Each channel runs separately, which reduces crosstalk and improves signal quality.
HART Protocol Support Enables digital connection with field devices using normal 4-20 mA analogue wire. Each channel is equipped with a separate HART modem.
Conformal Coating (HK version) offers greater protection against moisture, dust, and corrosive conditions, making it excellent for severe industrial situations.
Flexible Output Ranges Current outputs range from 0 to 20 mA and 4 to 20 mA, which can be configured per channel.
Advanced diagnostics. Open-circuit detection, short-circuit protection, and output ramping are included to prevent unexpected signal changes.
Buy currently uses Select Automation shop pricing and checkout.
Output & Signal Capabilities:
Channels: 8 isolated differential analogue output channels.
Signal Type:
Current: 0–20 mA and 4–20 mA.
Resolution: 15 bits across 24 mA range.
Overvoltage Protection: ±24V DC.
Startup Behaviour: Outputs default to 0 mA until diagnostics and configuration are complete.
HART Communication:
Modem Configuration: 1 dedicated HART modem per channel.
Protocol Support:
Command-response communication.
Point-to-point wiring.
Dual master support (e.g., controller + handheld communicator).
Estimated Scan Time: ~1 second per channel with HART enabled.
Diagnostics & Safety:
Ramping: Limits rate of output signal change to prevent abrupt transitions.
Open-Circuit Detection: Available in current mode.
Short-Circuit Protection: Built in.
Isolation: Channel-to-channel and channel-to-backplane isolation.
Mechanical & Environmental:
Module Type: Open style (requires installation in ControlLogix chassis).
Conformal Coating: Yes – enhanced protection against moisture and contaminants.
Compatible Software: Studio 5000 Logix Designer®.
Data Types: Selectable in software (e.g., Analog + HART PV).